Priority Type Event
Control module
LCD Display
Control module
LED
Delay Time
22 Trip Discharge temperature trip “Discharge Temp”
“Trip”
Flashing RED Max of ASCD and 2 min
23 W
arning Loss of communication
between control module& E2
“No Communication”
“Failsafe ON” (or OFF)
Flashing
GREEN
NA
24 W
arning sensor module failure “Sensor Module”
“Failure”
Flashing
GREEN
NA
25 W
arning Loss of Communication
(control to sensor module)
“No Communication”
“To Sensor module”
Flashing
GREEN
NA
26 W
arning Low oil pressure warning “Normal Running”
“Low Oil Pressure”
Flashing
GREEN
NA
27 W
arning Connection lost between CT &
sensor module
“Connection Lost”
“CT To Sensor”
Flashing
GREEN
NA
28 W
arning Unloader1 over-current
warning
“Normal Running”
“Unloader1 Short”
Flashing
GREEN
NA
29 W
arning Unloader2 over-current
warning
“Normal Running”
“Unloader2 Short”
Flashing
GREEN
NA
30 W
arning Unloader1 open circuit “Normal Running”
“Unloader1 Open”
Flashing
GREEN
NA
31 W
arning Unloader2 open circuit “Normal Running”
“Unloader2 Open”
Flashing
GREEN
NA
32 W
arning Open Thermistor “Normal Running”
“Fault Temp Probe”
Flashing
GREEN
NA
33 W
arning Unloader1 over-current
warning
“Normal Off”
“Unloader1 Short”
Flashing
GREEN
NA
34 W
arning Unloader2 over-current
warning
“Normal Off”
“Unloader2 Short”
Flashing
GREEN
NA
35 W
arning Unloader1 open circuit “Normal Off”
“Unloader1 Open”
Flashing
GREEN
NA
36 W
arning Unloader2 open circuit “Normal Off”
“Unloader2 Open”
Flashing
GREEN
NA
37 W
arning Open Thermistor “Normal Off”
“Fault Temp Probe”
Flashing
GREEN
NA
38 Normal
Normal Run “Normal Running” Solid GREEN NA
39 Normal
Normal Off “Normal Off” Solid GREEN NA
40 Normal
Anti Short cycle timer running “Anti short cycle”
“Time XX.X m Left”