Specifications

38
© 2012 Emerson Climate Technologies, Inc.
Printed in the U.S.A.
AE8-1368 R2
Unloader Short
Unplug the
connector to the
unloader coil
Is the coil
resistance less
than 5 ohms?
Replace the
unloader coil
Does the Unloader Short
fault still appear?
With the unloader
output unplugged,
force the unloader
stage “off” to
energize the circuit
Compressor harness short or
failed control module
Yes
No
Yes
Replace coil
(failure under
load)
No
The unloader short protects the harness and electronics from high current (2
s0.5 Amps) associated with a shorted coil or harness. The control module
must be reset to allow the unloader to be operated again.
6.17