Contactor Coil Lockout
Turn off the pilot circuit and
“open” the motor power
breaker.
Unplug the contactor output
leads at the contactor (or pilot
relay). Measure the contactor
(or pilot relay) coil resistance
Is the coil resistance less
than the mfgs’ minimum
specified?
Replace the relay
or contactor coil
Does the compressor
generate a “No 3-phase
power” fault?
With the contactor
output unplugged,
turn on pilot circuit
and send a “run”
command
Does the compressor still
generate a contactor coil
lockout?
Compressor harness short or
failed control module
- Unplug the contactor output
connectors in the terminal
box and repeat the test to
help determine the location
of the wiring short.
Yes
No
No Yes
Replace coil
(failure under
load)
Yes
The contactor coil lockout protects the circuit from high current (3 + 0.5
amps) resulting from a “shorted” coil or harness. The control module
must be re-set to clear the lockout.