Specifications

41
© 2012 Emerson Climate Technologies, Inc.
Printed in the U.S.A.
AE8-1368 R2
Protector Trip
This fault pertains to 2D and 3D compressors with internal line
break protectors. The presence of motor voltage without current
flow is the symptom used to detect a protector trip. Current flow
is measured by the Current Sensing Module (“CT”, for Current
Transducer)
Is the
compressor
running?
Normal Operation
The internal protector
has tripped. The
compressor will restart
when the motor has
adequately cooled
Possible Causes:
1.) Motor lead not passing through CT
2.) CT not plugged into sensor module, or pins
in connector not engaged
3.) Faulty CT – check resistance of CT through
pins 1 and 2 of the connector (see below)
4.) Faulty sensor module
Yes
No
View of the open end of
the CT connector that
plugs into the sensor
module
Resistance between pins
1 and 2 = 60 – 80 ohms
6.20