Phase Loss Trip / Lockout
A phase loss trip occurs if one or two phases of the motor are not
receiving voltage. The compressor will shut off and remain off for 5
minutes before trying again. If the phase loss occurs for 10
consecutive attempts, a lockout will occur. A lockout requires that
the module be reset to allow the compressor to run. Every
successful re-start will decrement the lockout counter by one.
Is full voltage present at
each terminal when the
contactor is loaded?
Voltage sensing
leads not
connected to motor
terminals.
Note that during a
light-load running
condition, the
missing-phase
voltage imbalance
may not be very
large
Normal Operation
Determine cause
of missing phase
or voltage
imbalance
YesNo
Missing Phase Voltage Imbalance
During Start-up
Missing Phase Voltage Imbalance
While Running