Specifications

45
© 2012 Emerson Climate Technologies, Inc.
Printed in the U.S.A.
AE8-1368 R2
No 3-Phase Power
No 3-phase power fault occurs if a run command has been sent
from the control module to the contactor (or pilot relay) and voltage
isn’t present at the motor terminals. This will not result in a lockout
condition; If demand remains, the compressor will continue to
attempt to run until voltage at the motor is present. This fault will
typically occur during start-up.
Is the compressor
contactor or pilot relay
closed?
Voltage sensing
leads not
connected to
motor terminals,
or faulty sensor
module
Open harness or
Faulty control module
relay
Is the
compressor
running?
Normal Operation
Main breaker is
thrown or other
compressor power
supply issue
Is 24v present at
“Contactor Output” of
harness in T-Box?
Faulty contactor
coil, pilot relay coil
or rack wiring
Yes No
Yes
No
Yes
6.24
Is the low voltage
harness connector
unplugged from the
control module?
No
No
Plug the
connector into
the control
module.
Yes