Rapid Compressor Cycling with
Constant Demand; Contactor Chatter
Inspect for:
Loose connection in the contactor coil power circuit
Loose connection at the white sensor module connector
that supplies 24V to the control module. Re-size the
connector pin sockets or replace the harness.
Reference 6.8 – Module Low Voltage Trip
High pressure switch intermittent open circuit. Refer to
6.3, High Pressure Discharge Pressure Trip. After
verifying that high head pressures are not the problem,
temporarily bypass the pressure switch to see if the
switch is the root cause.
Undersized transformer. Reference the appendix for
sizing of the transformer. This may occur if an unloader
has been added to the compressor as an aftermarket
upgrade.
Auxiliary contactor miswired into the pilot circuit