Comp Low Voltage Trip / Lockout*
*This condition will result in a Lockout after 10 consecutive events
Is the proper 3-phse
voltage being
supplied to the
compressor?
Correct Power
Supply Issue
Yes
Are the sensor module
voltage sensing lease
connected to the motor
terminals?
No
6.33
Connect as shown in
Figure 2.2
No
Confirm that the
CoreSense module has
been programmed with
the proper voltage setting
(refer to section 4.7)
Yes