User manual

FP series user manual
Allis Electric - 20 - Rev3. July 2005
2. Installation
For Mechanical Dry Contact
The DB9 Dry Contact Card offers three relay outputs for
custom- wired application. The figure below shows the
interface for the system connection:
PIN Definition of DB9 for Mechanical Dry Contact interface
PIN # of DB9
Function explanation I/O
1,2
BATTERY LOW -
normally closed state, will become
open during active state. (PIN 2 is common)
OUTPUT
3,5
POWER FAILURE -
normally open state, will become
closed during active state. (PIN 5 is common)
OUTPUT
4,5
POWER FAILURE - normally closed state, will
become open during active state. (PIN 5 is
common)
OUTPUT
6,7
Remote shut-down UPS - keep this pin at high
voltage (+5V~+12V), needs 500 ms to shut down
UPS. Activates at battery mode.
INPUT
8,9
FAULT - normally close state, will become open
during UPS fault. (PIN 9 is common)
OUTPUT
2.5.3.2 USB Card
When the connected computer only has USB ports, an optional USB 1.0 can be used in the
communication slot. A USB cable is supplied with the card.