User manual
FP series user manual 
Allis Electric           - 29 -           Rev3. July 2005 
3. Operation 
3.4 Configuration Settings   
Press the FUNCTION/TEST button and SET/ALARM SILENCE button at same time 
for one second.    Alarm will sound one beep; the unit is in Configuration Mode. 
There  are  eight  Bit  columns  at  the  bottom  of  the  graphic  LCD 
display.    From  left to right, they are identified as  Bit 7  to Bit  0.   
When the UPS is in Configuration Mode, Bit 0 will be lit.    Press the 
FUNCTION/TEST  button  to move  between  Bit  0  to  Bit  6.    When 
changing from Bit 0 to Bit 6, check to see if Bit 7 is lit.    If it is, then 
that located Bit is set.    Pressing the SET/ALARM SILENCE button 
will toggle between set and unset. 
Bit Definition Table 
Key Button
Setting 
Bit Definition 
SET/A
larm 
Button 
Status Setting
Bit 7 
On=lit Off=unlit 
Green Mode  Bit 3 
On: Disable Green Mode       
Off: Enable Green Mode   
Output 
Voltage
208V 
(100V)
220V 
(110V)
230V 
(115V)
240V 
(120V) 
Bit 1  Off  Off  On  On 
Function 
Button 
UPS INVERTER                     
OUTPUT 
VOLTAGE             
Bit 0  Off  On  Off 
On 
  Green Mode 
Enable/Disable Green Mode 
1.  Pressing the FUNCTION/TEST and SET/ALARM SILENCE buttons at the same time for 1 
second. Alarm will sound one beep; the UPS is in configuration mode . 
2.  Press the FUNCTION/TEST button until Bit 3 is lit.    If Bit 7 is lit, then Green Mode is 
disabled.    If Bit 7 is unlit, then Green Mode is enabled. 
3.  To change the setting, press the SET/ALARM SILENCE button once. 
4.  After changing to the desired setting, press the FUNCTION/TEST and SET/ALARM 
SILENCE buttons at same time for one second.    An audible beep will sound and the Green 
Mode setting is set. 
Bit 7      Bit 6      Bit 5     Bit 4      Bit 3      Bit 2      Bit 1      Bit 0 










