4. Maintenance 
4.3 Testing new batteries 
Start up the UPS with load added.    Press the FUNCTION/TEST button for three seconds to 
activate the self-test.    If the UPS switches back to Normal Mode after 10 seconds, then the 
batteries are good.    If it does not, then please check the battery cable or connections.   
Contact your sales representative for assistance. 
4.4 Recycling the used battery 
Do not discard the UPS, the battery pack, or batteries into the trash. Contact your local 
recycling or hazardous waste center for information on proper disposal of used battery pack 
and batteries. 
Consider  all  warnings,  cautions,  and  notes  before  replacing  batteries. 
Batteries  can  present  a  risk  of  electrical  shock  and  high  short  circuit 
current. The following precautions should be observed when working on 
batteries: 
 Remove watches, rings, and other metal objects. 
 Use tools with insulated handles. 
 Do not lay tools or metal parts on top of batteries. 
 Do not attempt to alter any battery wiring or connectors.    Attempting 
to alter wiring can cause injury. 
 Do  not  dispose  of  batteries  in  a  fire.    The  batteries  may  explode.   
Refer to your local codes for disposal requirements. 
 Do not open or mutilate the battery or batteries.    Released electrolyte 
is harmful to the skin and eyes.    It may be toxic. 
4.5 Fuse replacement 
The output fuse is located at the rear of the UPS.    Before changing the fuse, turn off the UPS 
and unplug the input cable from the AC source.   
1.  Press and rotate the fuse holder counter-clockwise.  
2.  Replace the fuse with one of similar type and rating.    Re-install the assembly into 
the UPS.    Press and rotate the fuse holder clockwise until it locks into position. 
3.  Reconnect the input power cord to the input AC source. 
4.  Restart the UPS. 