6. Appendix
6.2 Specifications
General specifications
The principal operating characteristics of the FP-Series UPS at 25°C ambient operating
temperature is shown below.
MODEL FP1000 FP1600 FP2500 FP3200
INPUT
Input Voltage
(Nominal input voltage)
230 V (160 ~ 276 V)
Nominal input Frequency 50 / 60 Hz ±5 Hz
Input PFC >0.98 @ full load
OUTPUT
Power 1000VA/700W
1600VA/1120W
2500VA/1750W
3200VA/2240W
Output Voltage
(Output Voltage Regulation)
208V / 220V / 230V / 240V
(Rated Voltage ± 2% )
Output Frequency 50/60HZ (Auto-tracking)
High Efficiency Mode
(AC to AC)
>86% >86% >88% >88%
Output T.H.D <3% at linear load
Overload Capacity Sustaining 50sec @ 108% load; 28sec @ 110~120% load;
15sec @ 120~130% load; 9sec @ 140~145% load;
Immediate Response @ 150%
Crest ratio 3:1
Transfer Time Zero for power failures or recoveries.
<4msec for UPS to Bypass or reverse.
BATTERY
Battery Packs 1×48VDC
Battery Pack
1×48VDC
Battery Pack
2×48VDC
Battery Pack (96V)
2×48VDC
Battery Pack (96V)
Typical Backup Time
(Full/Half load)
8/25 minutes 7/18 minutes 8/20 minutes 6/17 minutes
Battery Type Sealed VRLA 12V7AH; Hot-Swappable
Recharge Time to 90% 8 hours
Extended Battery Cabinet Extended Battery Module in 2U high
(comprises 2×48VDC Battery Packs)
MECHANICAL
Dimensions-Rackmount
(W×H×D in mm)
426 × 88(2U) ×
500mm
426 × 88(2U) ×
500mm
426 × 176(4U)
× 500mm
426 × 176(4U)
× 500mm
Weight(UPS / Battery Packs)
12/11.2 kgs 12/11.2 kgs 13.2/31.2 kgs 13.4/31.4 kgs
Total Weight 23.2 kgs 23.2 kgs 44.4 kgs 44.6 kgs
Conformance
EMI/RFI Compatibility EN50091-
2 Class B,
EN55022B
EN50091-
2 Class B,
EN55022B
EN50091-2 Class B,
EN55022B
EN50091-
2 Class B,
EN55022B
Safety Certifications CE , TUV / GS CE , TUV / GS CE , TUV / GS CE , TUV / GS