User manual

FP series user manual
Allis Electric - 46 - Rev3. July 2005
6. Appendix
Battery Run Time
RUN TIME CHART in Minutes
Output load
UPS Model
200 VA
(140 W)
400 VA
(280 W)
600 VA
(420W)
800 VA
(560W)
1000 VA
(700 W)
1500 VA
(1050 W)
2000 VA
(1400 W)
2500 VA
(1750 W)
3000 VA
(2100 W)
3200 VA
(2240 W)
FP 1000 59 32 18 12 8
+1 BM 260 134 83 58 50
+1BM + 1BMc 466 247 166 124 91
+2BM + 1BMc - 358 250 183 146
FP 1500 63 34 19 13 9 7
+1 BM 274 142 88 62 53 31
+1BM + 1BMc 491 260 175 131 96 60
+2BM + 1BMc - 377 264 193 154 92
FP 1600 67 38 21 15 10 8
+1 BM 279 148 93 64 55 33
+1BM + 1BMc 505 266 179 135 98 62
+2BM + 1BMc - 380 268 196 157 94
FP 2200 242 88 62 42 31 12 9
+1 BMc 373 241 184 98 75 43 27
+1BM + 1BMc - 487 244 172 140 62 52
+1BM + 2BMc - - 364 243 195 101 66
FP 2500 247 92 65 47 34 15 9 8
+1 BMc 379 244 186 107 78 44 29 20
+1BM + 1BMc - 491 249 179 142 66 53 41
+1BM + 2BMc - - 366 255 197 104 68 58
FP 3000 253 94 67 49 36 18 11 8 6
+1 BMc 383 246 189 109 79 49 29 21 16
+1BM + 1BMc - 493 153 182 147 69 54 42 31
+1BM + 2BMc - - 367 259 202 106 69 59 49
FP 3200 255 95 69 50 36 19 12 9 7 6
+1 BMc 385 247 190 111 81 50 30 21 17 16
+1BM + 1BMc - 495 156 183 148 70 55 43 32 30
+1BM + 2BMc - - 369 261 204 107 70 60 50 48
Indicates time not calculated, contact sales representative for details.