  Battery Run Time 
RUN TIME CHART in Minutes 
Output load
UPS Model 
200 VA 
(140 W)
400 VA 
(280 W)
600 VA 
(420W)
800 VA 
(560W) 
1000 VA
(700 W)
1500 VA
(1050 W)
2000 VA
(1400 W)
2500 VA
(1750 W)
3000 VA
(2100 W)
3200 VA
(2240 W)
FP 1000  59  32  18  12  8           
+1 BM  260  134  83  58  50           
+1BM + 1BMc  466  247  166  124  91           
+2BM + 1BMc  -  358  250  183  146           
FP 1500  63  34  19  13  9  7         
+1 BM  274  142  88  62  53  31         
+1BM + 1BMc  491  260  175  131  96  60         
+2BM + 1BMc  -  377  264  193  154  92         
FP 1600  67  38  21  15  10  8         
+1 BM  279  148  93  64  55  33         
+1BM + 1BMc  505  266  179  135  98  62         
+2BM + 1BMc  -  380  268  196  157  94         
FP 2200  242  88  62  42  31  12  9       
+1 BMc  373  241  184  98  75  43  27       
+1BM + 1BMc  -  487  244  172  140  62  52       
+1BM + 2BMc  -  -  364  243  195  101  66       
FP 2500  247  92  65  47  34  15  9  8     
+1 BMc  379  244  186  107  78  44  29  20     
+1BM + 1BMc  -  491  249  179  142  66  53  41     
+1BM + 2BMc  -  -  366  255  197  104  68  58     
FP 3000  253  94  67  49  36  18  11  8  6   
+1 BMc  383  246  189  109  79  49  29  21  16   
+1BM + 1BMc  -  493  153  182  147  69  54  42  31   
+1BM + 2BMc  -  -  367  259  202  106  69  59  49   
FP 3200  255  95  69  50  36  19  12  9  7  6 
+1 BMc  385  247  190  111  81  50  30  21  17  16 
+1BM + 1BMc  -  495  156  183  148  70  55  43  32  30 
+1BM + 2BMc  -  -  369  261  204  107  70  60  50  48 
Indicates time not calculated, contact sales representative for details. 