Releasing-Circuit Wiring Length
The releasing-valve is dependant on sufficient releasing-voltage at the solenoid-terminals to provide actuation. 
Releasing-valve actuation cannot occur when losses in the releasing circuit prevent sufficient voltage from occurring 
at the solenoid-terminals. Installers must determine the maximum wire length that can safely provide operating 
voltage at the solenoid terminals to negate losses of the releasing circuit. 
Determine the maximum wire length that can safely operate a Fire Protection Service Valve.
To determine the maximum wire length of the releasing circuit:
Summary of Parameters
The table below summaries parameters for determining the maximum wire length (L
max
) of the circuit:
1 Calculate the minimum voltage (Vout
min
) at the EXTING. terminals of the Quaestor-SZU Releasing Fire Control Panel.
2  Calculate the minimum operating-voltage (Vop
min
) of the Solenoid Release Valve (SRV).
3  Calculate the voltage-drop of the circuit (V
drop
) when the EXTING. output is at the minimum level (Vout
min
) and 
when the operating-voltage of the SRV is at the minimum level (Vop
min
).
4  Calculate the maximum current of the circuit (I
max
) when the SRV operates at the minimum level (Vop
min
).
5  Determine the wire-resistance-per-foot of the cabling (R
wire
) in the circuit. 
6  Calculate the maximum wire length (L
max
) of the circuit when connecting the SRV to the EXTING. terminals.
Parameter Description Equation
Vout
min
Minimum voltage at the EXTING. Output.
UL  864  specifies  that  the  Quaestor-
SZU  Releasing  Fire  Control  Panel 
operate a minimum output-voltage 85% 
below the nominal rating.
Vout
min
 = Vout
nominal
 x 85%
Vop
min
Minimum operating-voltage of the SRV.
UL 429 specifies that the SRV operate a 
minimum voltage 65% below the nominal 
rating.
Vop
min
 = VSRV
nominal
 x 65%