Specifications
Wiring Diagram D
SHM80001
SAFETY HI-TECH
Quaestor-SZU Releasing Fire Control Panel - Installation and Operation Manual
Revision E03.04
126 of 155
11
Notification Appliance Circuit
NAC Synchronization
Quaestor-SZU Releasing Fire Control Panel
supports special application outputs of NAC 1 and NAC 2
when operating:
Amseco NAC devices with Amseco synchronization
modules
Gentex NAC devices with Gentex synchronization modules
System Sensor NAC devices with System Sensor
synchronization modules
Wheelock NAC devices with Wheelock synchronization
modules
NAC channels 1 and 2 of the Quaestor-SZU Fire Control Panel
provide single and dual circuit synchronization. Single circuit
synchronization provides a synchronized output on one channel
of two NAC channels. Dual circuit synchronization provides a
synchronized output on NAC 1 and NAC 2.
Maximum Current
A maximum current of 1.5 Amps is available for powering
NAC 1, NAC 2 and NAC 3 when a maximum load of 500 mA
exists on any one of the NAC outputs.
File: S8485, Part Number: Man-SHM80004
Revision E07.03, Date: 26 March 2013