Specifications

Wiring Diagram D
SHM80001
SAFETY HI-TECH
Quaestor-SZU Releasing Fire Control Panel - Installation and Operation Manual
Revision E03.04
126 of 155
11
Notification Appliance Circuit
NAC Synchronization
Quaestor-SZU Releasing Fire Control Panel
supports special application outputs of NAC 1 and NAC 2
when operating:
 Amseco NAC devices with Amseco synchronization
modules
 Gentex NAC devices with Gentex synchronization modules
 System Sensor NAC devices with System Sensor
synchronization modules
 Wheelock NAC devices with Wheelock synchronization
modules
NAC channels 1 and 2 of the Quaestor-SZU Fire Control Panel
provide single and dual circuit synchronization. Single circuit
synchronization provides a synchronized output on one channel
of two NAC channels. Dual circuit synchronization provides a
synchronized output on NAC 1 and NAC 2.
Maximum Current
A maximum current of 1.5 Amps is available for powering
NAC 1, NAC 2 and NAC 3 when a maximum load of 500 mA
exists on any one of the NAC outputs.
File: S8485, Part Number: Man-SHM80004
Revision E07.03, Date: 26 March 2013