Specifications

Wiring Diagram D
SHM80001
SAFETY HI-TECH
Quaestor-SZU Releasing Fire Control Panel - Installation and Operation Manual
Revision E03.04
129 of 155
14
File: S8485, Part Number: Man-SHM80004
Revision E07.03, Date: 26 March 2013
Exting.
Releasing output: 18 to 28 VDC, with 1.0 Amp
maximum load for 5 minutes and voltage reversing
DC. Maximum line-voltage-drop: 2.4 VDC
Fused at 1.6 Amps
Manufacturers Model
Safety Hi-Tech
SH21006403
Safety Hi-Tech
SH21006403
Viking
11601
Viking
11602
Viking
11592
Viking
11595
Snap-Tite
2823A-2NB-A4F6
Viking
11591
Viking
11596
Sevo Systems
SOL EA45, The SOL EA45 is equivalent to Sevo
Systems 510006 and TLX Technologies PA0036-3
Kidde
K-45-8017, The K-45-8017 is equivalent to Kidde-
Fenwall 486500-01
Kidde
B6793-859, The B6793-859 is equivalent to Kidde-
Fenwall 81-100000-001
Victaulic
Series 753-E FireLock
Fire Eater
305450 Ci IS8B Solenoid
Fire Eater
305451 Ci IS8B Solenoid and Manual
Authorized Releasing Valves
The extinguishant release output of the Quaestor-SZUReleasing Fire Control
Panel is 1 Amp. All solenoids must operate using 1 amp or less.
The solenoid releasing valves above are authorized for use as Fire Protection-
Service Valves on the Quaestor-SZU Releasing Fire Control Panel.
Releasing Device Circuits