Specifications

Wiring Diagram D
6+0
6$)(7<+,7(&+
6+7&36=8 Releasing Fire Control Panel - Installation and Operation Manual
Revision E03.02
129a of 155
15
File: S8485, Part Number: Man-SHM80004
Revision E07.03, Date: 26 March 2013
Exting.
Releasing output: 18 to 28 VDC, with 1.0 Amp
maximum load for 5 minutes and voltage reversing
DC. Maximum line-voltage-drop: 2.4 VDC
Fused at 1.6 Amps
Manufacturers Model
ASCO
HV2185328
ASCO
8210G207
Manufacturers Model
Kentec Electronics
Sequential Activator —>FP-SA/GEN3.0
FirePro
Fixed Condensed Aerosol Extinguishing system
units —>FP-100S, FP-200S, FP500S, FP1200,
FP2000, FP-3000, FP-5700
Authorized Releasing Valves
The extinguishant release output of the Quaestor-SZU Releasing Fire Control
Panel is 1 Amp. All solenoids must operate using 1 amp or less.
The solenoid releasing valves above are authorized for use as Fire Protection-
Service Valves on the Quaestor-SZU Releasing Fire Control Panel.
Releasing Device Circuits (Continued)
Special Releasing Accessories