16
Abort Function
File: S8485, Part Number: Man-SHM80004
Revision E07.03, Date: 26 March 2013
Override
Operation
The abort function overrides the manual
release when the manual release is activated
before the abort.
The manual release overrides the abort
function when the abort is activated before
the manual release.
Connection
Monitored input EOL 6.8K Ohm +/- 5%
resistor, activation
impedance 470 Ohms