Specifications

UL 864 Permitted Configurations G
SHM80001
SAFETY HI-TECH
Quaestor-SZU Releasing Fire Control Panel - Installation and Operation Manual
Revision E03.04
144 of 155
Notice To Users, Installers, Authorities Having
Jurisdiction, and ot
her involved parties.
This
product
in
corporates field-programmable software.
In order for the product To comply with the requirements
in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864 9th Edition, certain
programming features or options must be limited To specific values or not used at all as indicated below.
Program Feature or Option Permitted in UL 864 ? (Y/N) Possible Settings Settings Permitted
In UL 864
NAC Output Delay
Code: C00 To C09
N 30 seconds - 9 minutes 0 minutes
Zone 1 and Zone 2 Detectors
Trigger Automatic Release
Code: C11
Y Enable / Disable Enable / Disable
Zone 2 and Zone 3 Detectors
Trigger Automatic Release
Code: C12
Y Enable / Disable Enable / Disable
Zone 1 and Zone 3 Detectors
Trigger Automatic Release
Code: C13
Y Enable / Disable Enable / Disable
Zone 1 and Zone 2 or
Zone 2 and Zone 3 or
Zone 1 and Zone 3 Detectors
Trigger Automatic Release
Code: C14
Y Enable / Disable Enable / Disable
Zone 1 and Zone 2 and
Zone 3 Detectors Trigger
Automatic Release
Code: C15
Y Enable / Disable Enable / Disable
Zone 1 or Zone 2 or Zone 3
Detectors Trigger Automatic
Release
Code: C16
Y Enable / Disable Enable / Disable
Appendix G
UL 864 Permitted Configurations