Specifications
 SHM80001
SAFETY HI-TECH  
Quaestor-SZU Releasing Fire Control Panel - Installation and Operation Manual 
Revision  E03.04
Underwriters Laboratories (UL)
File number (S 8485)
Fire Alarm Equipment
SAFETY HI-TECH
The model series SHC8000 of the Quaestor-SZU Releasing Fire Control Panel is suitable as follows:
•
Local Signaling Unit, Cross Zone and Releasing 
• Commercial protected-premises control unit
• Types of signaling services are SLC Class B, Style 4, NFPA 72 conventional IDC Class B and 
 Style C or Class B, Style B, automatic fire alarm, manual fire alarm
• Non-coded Signaling 
• Compatibility IDAXT0110
Install detectors with spacing as specified in section 90.19 of UL 864, 9th edition where units employing the multiple detector operation shall include 
guidelines for installing of a minimum of two detectors in each protected space and to reduce the detector installation spacing to 0.7 times the linear 
spacing in accordance with National Fire Alarm Code, NFPA 72. Also reference 55.3.1 and 55.3.2 of UL 864, 9th edition for these detector spacing 
requirements.
NFPA
SAFETY HI-TECH 
This product satisfies releasing operation under:
• Carbon dioxide extinguishing systems, NFPA 12
• Halon 1301 fire extinguishing systems, NFPA 12A
• Sprinkler systems, NFPA 13
• Water spray fixed systems for fire protection, NFPA 15 
• Foam-water sprinkler and foam-water spray systems, NFPA 16
• Dry chemical extinguishing systems, NFPA 17
• Wet chemical extinguishing systems, NFPA 17A
• Water mist, NFPA 750
• Clean agent fire extinguishing systems, NFPA 2001 