Specifications

SHM80001
SAFETY HI-TECH
Quaestor-SZU Releasing Fire Control Panel - Installation and Operation Manual
Revision E03.04
Underwriters Laboratories (UL)
File number (S 8485)
Fire Alarm Equipment
SAFETY HI-TECH
The model series SHC8000 of the Quaestor-SZU Releasing Fire Control Panel is suitable as follows:
Local Signaling Unit, Cross Zone and Releasing
Commercial protected-premises control unit
Types of signaling services are SLC Class B, Style 4, NFPA 72 conventional IDC Class B and
Style C or Class B, Style B, automatic fire alarm, manual fire alarm
Non-coded Signaling
Compatibility IDAXT0110
Install detectors with spacing as specified in section 90.19 of UL 864, 9th edition where units employing the multiple detector operation shall include
guidelines for installing of a minimum of two detectors in each protected space and to reduce the detector installation spacing to 0.7 times the linear
spacing in accordance with National Fire Alarm Code, NFPA 72. Also reference 55.3.1 and 55.3.2 of UL 864, 9th edition for these detector spacing
requirements.
NFPA
SAFETY HI-TECH
This product satisfies releasing operation under:
Carbon dioxide extinguishing systems, NFPA 12
Halon 1301 fire extinguishing systems, NFPA 12A
Sprinkler systems, NFPA 13
Water spray fixed systems for fire protection, NFPA 15
Foam-water sprinkler and foam-water spray systems, NFPA 16
Dry chemical extinguishing systems, NFPA 17
Wet chemical extinguishing systems, NFPA 17A
Water mist, NFPA 750
Clean agent fire extinguishing systems, NFPA 2001