Specifications
Programming and Operating 4
SHM80001
SAFETY HI-TECH
Quaestor-SZU Releasing Fire Control Panel - Installation and Operation Manual
Revision E03.04
42 of 155
Code Function Description
C2A LOCAL FIRE relay operates
upon released signal
Local fire relay operates only when extinguishant is released rather
than upon a fire condition
C2b Extinguishant output on until
reset
Extinguishant output remain on after release until panel is reset. (from
software version 1.2 onwards only)
C2C LOW P. SWITCH (Low pressure
switch normally closed)
Low Pressure switch input normally looks for open contact closure on
activation, enables normally closed switch to be used.
C2D Delay the indication of a
Power Trouble by 30 minutes
The Power Trouble indication is delayed by 30 minutes unless a
Battery Low trouble exists. When a Battery Low trouble is reported,
the delay of the Power Trouble indication is cancelled and the
Power Trouble and Battery Low trouble are immediately reported.
C31 Zone 1 alarm from detector
delayed
NAC outputs are delayed by time set at options 0-9 when zones are
triggered by detector only. Any combination can be selected.
C32 Zone 2 alarm from detector
delayed
C33 Zone 3 alarm from detector
delayed
C41 Zone 1 alarm from pull station
delayed
NAC outputs are delayed by time set at options 0-9 when zones are
triggered by pull station only. Any combination can be selected.
C42 Zone 2 alarm from pull station
delayed
C43 Zone 3 alarm from pull station
delayed