Code Function Description
E00 Panel can be reset immediately
after discharge output has
operated
To allow reset of the panel to be prohibited before the extinguishant
discharge has fully completed.
E01
TO
E29
Panel can be reset 1 minute to
29 minutes after discharge
output has operated
E30 Panel can be reset 30 minutes
after discharge output has
operated
-00 No extinguishant delay Time delay between activation and extinguishant release output
operating. This menu option is accessed using the lamp test (+100)
button. The time is adjusted using the Mode button for 10’s and the
Select button for 5’s. Once the time is selected the Enter button is
used to store the value.
-05 5 second extinguishant delay
-10
TO
-55
Increment extinguishant delay in
five second steps
-60 60 second extinguishant delay
060 Sets extinguishant duration time
for 60 seconds
Time that extinguishant release output is activated. This menu option
is accessed using the lamp test (+100) button. The time is adjusted
using the Mode button for 10’s and the Select button for 5’s. Once the
time is selected the Enter button is used to store the value. Panel can
not be reset until this time has expired except by operating the
terminate extinguishant switch located under the front cover.
060
TO
295
Increment extinguishant duration
time in five second interval
300 Sets extinguishant duration time
for 300 seconds