Specifications

Supplementary Devices 6
SHM80001
SAFETY HI-TECH
Quaestor-SZU Releasing Fire Control Panel - Installation and Operation Manual
Revision E03.04
67 of 155
The figure below illustrates DIP switch settings on the Status Unit and Ancillary Board:
Figure 6-8
DIP Switch Settings
Adding Status Units and Ancillary Boards
When the system is powered, it will search for connected status units and/or ancillary boards. When new or additional
status units/ancillary boards are added to the system, these will be shown on the display when the system is first
powered.
Status units are shown as Pux and ancillary boards are shown as Pox (where x is the address of the unit found). The
select key can be used to view all of the status units/ancillary boards that the system has found. These should be
checked to ensure that the same number of devices that have been connected are found by the system.
For the system to accept these into its memory, the procedure below must be followed.
1 Operate the Enable Controls key-switch.
2 Enable the Write Enable Switch (push to the right) – Access level 3.
3 The display will show Pux for status units and Pox for ancillary boards that are found (where x is the address of
each unit) and the dot in the display will be flashing. Operate the Enter button which will accept the displayed
unit and step through to the next unit found.
4 When the Enter button does not step on to any other units, all devices have been accepted.
5 Disable the Write enable switch (push to the left).
6 Disable the Enable controls key-switch.
7 The panel should return to the normal, quiescent condition.