Specifications
Specifications A
SHM80001
SAFETY HI-TECH
Quaestor-SZU Releasing Fire Control Panel - Installation and Operation Manual
Revision E03.04
77 of 155
Releasing Outputs
Relay Ratings
Exting. Releasing output: 18 to 28 VDC, with 1.0 Amp maximum load for
5 minutes and voltage reversing DC.
Maximum line-voltage-drop: 2.4 VDC
Fused at 1.6 Amps
Extract Power Factor: 1.0
Relay Function: Common
EXTRACT (NO) and (C): 30 VDC @ 1A Amp maximum, volt free
change over contact
Extinguishant Output
End of Line
1N4004 diode supplied in terminals
Extinguishant Output Delay Adjustable 0 to 60 seconds (+/- 10%) in 5 second steps
Extinguishant Duration Adjustable 60 to 300 seconds (+/- 10%) in 5 second steps
Short Circuit Threshold Adjustable
Terminals Ratings
TROUBLE RELAY
(NC), (C) and (NO)
Power Factor: 1.0
Relay Function: Common
30 VDC @ 1A maximum, volt free change over contact
LOCAL FIRE
(NC), (C) and (NO)
Power Factor: 1.0
Relay Function: Common
30 VDC @ 1A maximum, volt free change over contact
FIRE RELAY
(NC), (C) and (NO)
Power Factor: 1.0
Relay Function: Common
30 VDC @ 1A maximum, volt free change over contact