Specifications
Equipment list B
Notification Appliances
Outputs of NAC 1 and NAC 2 of the Quaestor-SZU Releasing Fire Control Panel operate in a special application
mode when conforming to specific levels of continuous DC. Outputs meet these requirements when NAC
currents
do not exceed 500 mA on NAC 1 or NAC 2 with the combined currents not to exceed 1.0 A.
The Quaestor-SZU Releasing Fire Control Panel supports special application outputs of NAC 1 and NAC
2
when operating:
•
Amseco NAC devices with synchronization modules
•
Gentex NAC devices with synchronization modules
•
System Sensor NAC devices with synchronization modules
•
Wheelock NAC devices with synchronization modules
Synchronization
NAC channels 1 and 2 of the Quaestor-SZU Releasing Fire Control Panel provide single and dual circuit
synchronization. Single circuit synchronization provides a synchronized output on one channel of two NAC
channels. Dual circuit synchronization provides a synchronized output on NAC 1 and NAC 2.
The Quaestor-SZU Releasing Fire Control Panel provides synchronization for the outputs of NAC 1 and NAC
2
when operating external synchronization devices and NAC devices from Amseco, Gentex, System Sensor or
Wheelock.
Synchronization Modules
Synchronize the special application output of NAC 1 and NAC 2 using the UL listed and compatible synchronization
modules described in the table below:
Manufacturer
Manufacturer
Sync Module
Manufacturer
&
Safety High-Tech
NAC
Device
Amseco
SMD10-3A ***
Gentex
AVSM-R (Red)
AVSM-W (White)
***
System Sensor
MDL (Red)
MDLW (White)
***
Wheelock
SM-24-R
DSM-24-R
***
Connect one 10K EOL resistor, SHE8000I to the output of each Synchronization Module.
*** All NAC devices that are compatible with the synchronization modules above are compatible for use with the
Quaestor-SZU Releasing Fire Control Panel.
SAFETY HI-TECH
Quaestor-SZU Releasing Fire Control Panel - Installation and Operation Manual
Revision E03.04
SHM80001