User's Manual

--------------------------------------------------------------------------------18/26--------------------------------------------------------------------------------
4.14 RNR
Setting RNR not to 0 activtes the RNR fuction. Then each reader answer is preceded by a reader num-
ber and a space character as well (i.e 15 <SP>).
input format: RNR <SP> parameter <CR>
Parameter Function
0 RNR function not active
1 ... 9 the one-digit reader number and <SP> is
preceded to each reader answer
10 ... 99 the two-digit reader number and <SP> is
preceded to each reader answer
output (example): 99 <CR> after entering RNR 99 <CR>
NAK#02 <CR> after entering RNR 1A <CR>
4.15 RST
With RST a warm start is executed. All changed parameter values (i.e. BD) become effecive. The relays
and error LEDs are cleared.
input format: RST <CR>
output: Version number <CR> if EC=1, otherwise <CR> is output only
4.16 TOR
Timeout for the reader. TOR is used in operation mode 2 as maximum gating time for a reading process
(see chapter 2.4). The length of the maximum gating time results from the equation gating_time = TOR
* TB.
The time constant TB (Time Base) has always the default value 100ms.
input format: TOR <SP> parameter <CR>