User manual

50
Description Adjustable parameters Presetting
Relay
configuration
[UPS ok], [on bypass],
[on Economical mode (ECO)],
[on High efficiency mode (ECO+)],
[on battery], [battery low],
[battery fault], [battery missing],
[Fan fault], [Summary Alarm]
UPS ok
Control
Commands
from
Serial Port
[enabled] [disabled]
If Enabled, control commands are
accepted through Serial & USB port
and cards in the communication slot.
If Disabled, configuration and load
control commands are restricted to
LCD panel only.
enabled
Output
Voltage
[200V], [208V], [220V], [230V], [240V],
[auto-sensing]
Setting only available in UPS stand-by
mode.
auto-sensing
Output
Frequency
[50Hz], [60Hz], [auto-sensing]
Setting only available in UPS stand-by
mode.
auto-sensing
Load Alarm
Level
(Overload)
[10%], [20%], [30%], ...[100%]
If 100%, the UPS issues an Output
Overload alarm at load >
100%.
NOTE : Output Overload Level 1 by
default is set to 100% and is
configurable from 10% to
100% in 10% increments
through the LCD setting menu.
This allows customers to be
alerted before the UPS has
reached its rated capacity
limits.
100%
Power
strategy
[High performance mode (normal)],
[Economical mode (ECO)],
[High efficiency mode (ECO+)],
[converter]
Setting only available in UPS stand-by
mode.
normal