User's Manual

Protect PV.500 Operating Instructions
56 of 73 80000041664 BAL
7.1.4.3 Configuring Modbus Data Transmission
T
o access the X5 data transmission configuration, you must press
<2> in the main menu:
Figure 21 Modbus/JBus data transmission configuration
Press one of the following keys in the “X5 Data Transmission”
menu:
<1-7> to set the baud rate.
<n,e,o> to set the parity.
<8,9> to set the number of stop bits.
<CR> to accept the set values. The configuration is finished
and the main menu is opened again.
<ESC> to cancel the configuration. This opens the main menu.
The Modbus factory setting is: 19200 8 E 1.