Power Supply User Manual

14
3.4 Technical Data
Type power
PROTECT C. 1000 (S) 1000 VA (cos ϕ = 0.7 lag.)
700 W
PROTECT C. 2000 (S) 2000 VA (cos ϕ = 0.7 lag.)
1400 W
PROTECT C. 3000 (S) 3000 VA (cos ϕ = 0.7 lag.)
2100 W
UPS Input (single phase)
Rated input voltage 220 / 230 / 240 Vac
Voltage tolerance range 160 Vac – 300 Vac ± 5 Vac
Bypass 80 Vac – 264 Vac
Nominal frequency 50 Hz / 60 Hz
(automatic detection)
Frequency tolerance range ± 4 Hz
Current consumption at full load (max.)
PROTECT C. 1000 (S) 7 A
PROTECT C. 2000 10 A
PROTECT C. 2000 S 12 A
PROTECT C. 3000 (S) 16 A
Input power factor
λ
0.96
Connection Non-heating appliance
connector
Datalines RJ11 (phone, fax, modem)
overvoltage protection RJ45 (Ethernet 10/100MBit/s)
UPS Output (single phase)
Rated output voltage 220 / 230 / 240 Vac ±2 %
(configuration via software
“CompuWatch”)
Nominal frequency 50 Hz / 60 Hz ± 0,2 %
(depending on mains)
Voltage waveform Harmonic distortion
4 % THD (linear load)
7 % THD (non-linear load)