The original carton provides effective protection against damage
and should be kept in case the device has to be transported
again at a later date.
Always keep plastic bags away from babies and children to
prevent suffocation.
Handle the components with care. Think of their weight and have
a second person to assist with lifting.
4.2 Installation location
The PROTECT D. is designed to be installed in a protected
environment. When choosing that location, make sure that there
is adequate ventilation and other appropriate environmental
conditions.
The PROTECT D. is air-cooled. Do not block the
vents!
The UPS and its battery modules in particula
r
should preferably be operated at room temperature
(between 15°C and 25°C).
Install the devices in a room that is dry, relatively dust-free and
free of chemical vapors.
Make sure that no magnetic storage media are stored and
/ or
operated in the vicinity of the PROTECT D.
Check the type plate to make sure that the voltage
and frequency specifications match those of you
r
load segments.
4.3 Assembly
For the rack installation of the UPS system and its external
battery units (special accessory), please note the following:
• To prevent vibration and jarring, the installation location has
to have adequate stability.
• Make sure the rack is able to support the installation,
particularly when external battery units (special accessory)
are used.
• Install the units so that there is adequate air circulation.
Make sure there is at least 100 mm of free space behind the