Power Supply User Manual

48
”Control” / Command Description
Go to
Bypass
/ Normal
Possibility to change operation mode.
If the UPS is not in Normal Mode or Bypass
Mode this option is not used and should not
be displayed as a control option.
Battery Test Schedule Battery Test: yes | Cancel Battery
test: no Starts a manual battery test.
Reset Error State Reset Alarms: yes | no
Manually clears any latched alarms, such as
bad battery detected or DC Bus over voltage/
under voltage.
If a bad battery alarm was also active, reset
the battery test status to “Not Tested”.
Load Segments Load segment 1: on | off
Load segment 2: on | off
These on/off commands override automatic
load segment on/off controls made by the
Automatic Start Delay and Automatic On
Battery Shutdown settings.
i
Configuring Load Segments
Load segments are sets of receptacles that can be
controlled by power management software o
r
through the display, providing an orderly shutdown
and startup of your equipment. For example, during
a power outage, you can keep key pieces o
f
equipment running while you turn off othe
r
equipment. This feature allows you to save battery
power and to get a controlled shutdown and later by
using the time-delayed switching-on a controllable
reboot of the network devices.
Load segment 0: The highest level outlets (directly
feeded by UPS output – not manageable)
Load Segment 1 and 2: Outlets for loads, which
should be controlled during operation, that means
which should be manageable.