Hoods can only be used safely with appliances connected to a
chimney if the room and/or flat (air/environment combination) is
ventilated from outside using a suitable ventilation hole approxi-
mately 500-600 cm
2
large to avoid the possibility of a depression
being created during operation of the hood.
If you have any doubts, contact the relevant controlling authority
or building inspector’s office.
Since the rule for rooms with fuel burning appliances is “outlet
hole of the same size as the ventilation hole”, a hole of 500-600
cm
2
, which is to say a larger hole, could reduce the performance
of the extractor hood.
If the hood is used in its recirculation mode, it will operate simply
and safely in the above conditions without the need for any of the
aforementioned measures.
When the hood is used as an extractor,the following rules must
be followed to obtain optimal operation:
short and straight outlet hose
keep bends in outlet hose to a minimum
never install the hoses with an acute angle, they must always
follow a gentle curve only
keep the hose as large as possible (100 or 120 mm Ø min.).
Failure to observe these basic rules will drastically reduce the
performance and increase the noise levels of the extractor hood.
Where flexible ducting is fitted the length should be no more
than:
— 3 metres with one 90° bend
— 2 metres with two 90° bends.
Bends of more than 90° will reduce the efficiency of the hood
and reduce the air flow.
Electrical connections
Please ensure that the voltage and current indicated on the rating
plate agree with the voltage of your electricity supply.
If your appliance has been equipped with a mains lead with a
moulded-on type plug, you must comply with the following
regulations:
The plug moulded on to the lead incorporates a fuse. For
replacement, use a 5 amp BS1362 fuse. Only ASTA approved or