Specifications

56
© Systeme Lauer GmbHAEG250PX-Expander driver
D
D1.2.2 The PCS maxi driver variables
COM_TIMEOUT: PCS time-out time
The time-out time determines the maximum admissible time for the processing of
the job package in the programmable controller. The default is 2000ms. Admissible
values for the variable are 1000ms to 9999ms (= 1 to 9.9 sec.).
COM_DAT_PL: Start address of the I/ O buffer in the PLC
Determines the first used flag word in the programmable controller for the data
interchange area. Thereby, the variable has an offset function. The possible values
for flag words are 1 to 15000. The default setting is 1256. Therefore, flag word
1256.
COM_MAXLEN: Maximum number of the packages per communication cycle.
In a communication cycle, the PCS forms sub-packages for each task. The number
of these sub-packages can be limited. This results in reducing the time for a
communication cycle. This can be advantageous for fast jog operations (as far as
possible without variable display). On the other hand, the refreshing of variables
thereby takes longer. Limit this variable only if all other measures have not resulted
in sufficient time savings. The possible values are between 1 and 32. Default value
is 32.
Set the rotary switch at the rearside of the PCS to an arbitrary position 0..3.
The only baud rate is 19200 baud.
D.1.3 Connection of the PCS to the PLC
Warning!
Check the PCS function and also after parameterization and/or driver
installation. All parameterized functions must be examined. Otherwise
malfunctioning of the PCS and/or programmable controller are possible.
1. After you have configured the PCS, set the DIL-switches 8 and 9 at the rearside
of the PCS to OFF.
2. Supply operating voltage (19..33V) to the PCS. At least the ERR LED must light
now.
3. Load the AEG250PX expander block into the programmable controller.
4. Connect the programming interface of the programmable controller to the PCS
using the PCS 778 adapter cable.
5. Switch the programmable controller to RUN. If the A 2.1 ERROR output lights,
then the E2.1 restart input must be set.
6. Now, the ERR LED at the PCS must be deactivated. Idle text 0 appears on the
PCS display. If this should not be the case, then continue reading under section
D1.5.
First commissioning