User`s guide

50 UPS 20-30 kVA, 230 V 50/60 Hz output
Users Guide
1026743
Revision B
13. Technical data
Standards
UPS 20 kVA 30 kVA
Safety IEC 62040-1-1, EN 62040-1-1 and EN 60950
EMC EN 50091-2
Product IEC 62040-3 and EN 62040-3
Environment
UPS 20 kVA 30 kVA
Amb. temperature 0 to +40°C (electronics), 15 to +25°C (batteries)
Relative humidity 0 to 95%, no condensation allowed
Altitude <1000 m above sea level
Vibration IEC 68-2-6; max. 0.3 mm (2 to 9 Hz), max. 1 m/s2 (9 to 200 Hz) sinusoidal
Maintenance configuration
UPS 20 kVA 30 kVA
Dimensions
- Width
- Depth
- Height
494 mm
762 mm
1684 mm
Weight
- no battery
- 36 battery
- 72 battery
- 108 battery
- 144 battery
200 kg
300 kg
400 kg
500 kg
600 kg
Colour RAL 9005 black
Characteristics
Powerware 9155 20 kVA 30 kVA
Efficiency
- nominal load
Up to 93%
Up to 93%
Heat losses <1600 W <1900 W
Backup time
- load pf 0.7
- temperature 25°C
5 min (36 bat 9Ah)
13 min (72 bat 9Ah)
22 min (108 bat 9Ah)
31 min (144 bat 9Ah)
-
7 min (72 bat 9Ah)
13 min (108 bat 9Ah)
20 min (144 bat 9Ah)
Noise (ISO 7779) 50 - 53 dB(A) depending on the load 50 - 53 dB(A) depending on the load