Power Supply User Manual

51
7.3.5 IDENTIFICATION
Activate this menu item to view the following sub-menu items:Type / Model”,
“Part number”, “Serial numberand finally the current “UPSrmware” version
one after the other.
7.3.6 SETTINGS
The following table provides you with a detailed description of the possible user
settings using the UPS operating panel:
”Control/ Command Description
Go to Bypass / Normal Possibility to change operation mode.
Menu item visible only when the UPS is currently
in Bypass or Normal Mode.
Battery Test Conducts battery test after confirmation.
Cancellation possible at any time as needed.
Reset Error State Resets alarm messages
Manually clears any active alarms, such as battery fault
detected or DC Bus over / under voltage.
With an active battery fault alarm, the battery test status
will also simultaneously reset to “Not Tested”.
Description Adjustable parameters Presetting
Change Language [English], [German], [French], [Spanish],
[Russian]
NOTE: Language selection order depends
on the current selection.
English
User Password [[enabled<AAAA>], [disabled]
If Enabled, select character between A~z
and numbers between 0~9.
NOTE: If you enter an incorrect password, the
message “Incorrect Password” appears. Press
any button to return to the password screen
and retry the password.
disabled