Power Supply User Manual

53
Description Adjustable parameters Presetting
Load Alarm Level
(Overload)
[10%], [20%], [30%], ... [100%]
NOTE: The adjustment is configurable in
10% increments so a possible UPS overload
can be detected early.
100%
Power strategy [High performance mode (normal)],
[Economical mode (ECO)],
[converter] - Setting only available in
UPS stand-by mode.
normal
Start w / o mains [enabled], [disabled]
UPS start from battery supply
enabled
Battery Saving
Mode
[disabled], [10%], [20%], ...[100%]
On battery operation the UPS output
is turned off as soon as the battery capacity
is below the selected level.
disabled
Alarm for phase
error
[enabled], [disabled] disabled
Charger output
voltage / cell
Float charging voltage per battery cell
2.21V, 2.22V, 2.23V, 2.24V, 2.25V, 2.26V,
2.27V, 2.28V, 2.29V, 2.30V, 2.31V
2.28V
Battery charge
capability %
to restart
[0%], [10%], [20%],[100%]
UPS switches consumers only after reaching
the preset minimum battery threshold
capacity.
0
Automatic
battery test
[enabled], [disabled] enabled
Periodic
battery tests
[daily], [weekly], [monthly] weekly
Automatic battery tests run according toperiodic battery test”, unless disabled.
During the test, the UPS transfers to Battery mode and discharges the batteries
for about 20 seconds under the existing load.