Installation guide

UPS 40-160 kVA, 400 V 50/60 Hz output
Users and Installation Guide
1023294
Revision C
10
3 UPS installation
Before installing the UPS systems read and understand how this manual applies to the system
being installed. Use the procedures and illustrations in the following chapters to create a logical
plan for installing the system.
3.1 Planning installation
The UPS and accessories are delivered on a specifically designed pallet that is easy to move with
a forklift or a pallet jack. Make sure that the floor surface is solid and suitable for the wheeling
and heavy weight. Keep the UPS always in upright position and do not drop the equipment. Do
not either stack the pallets because of high-energy batteries involved and the heavy weight
Use a forklift or pallet jack to move the packaged cabinet to the installation site, or as close as
possible, before unpacking. Insert the forklift or pallet jack forks between the pallet supports on
the bottom of the unit. Set the pallet on a firm, level surface, allowing a minimum clearance of
3m on each side for removing the cabinet from the pallet.
Note!
If the UPS is not immediately installed the following must be remembered:
• TheUPSshouldbestoredintheoriginalpackingandshippingcarton.
• DonottilttheUPScabinetmorethan10°fromverticalorcabinetmaytipover.
• Therecommendedstoringtemperatureisbetween+15°…25°.
• Theequipmentmustalwaysbeprotectedfrommoistureandweather.
The life of the UPS system is adversely affected if the installation does not meet the following
guidelines:
• Thesystemmustbeinstalledonaleveloorsuitableforcomputerorelectronicequipment.
• Thesystemmustbeinstalledinatemperatureandhumiditycontrolledindoorareafreeof
conductive contaminants.
• TheUPScabinetusesforcedaircoolingtoregulateinternalcomponenttemperature.Air
inlets are in the front of the cabinet and outlets are in the top. You must allow clearance in
front of and above each cabinet for proper air circulation.
The operating environment must meet the weight, clearance, and environmental requirements
in the technical specification.