Installation guide

UPS 40-160 kVA, 400 V 50/60 Hz output
Users and Installation Guide
1023294
Revision C
40
6.3 Mimic Screen
To select the Mimic screen from the Events, Meters, Controls, or Setup screens, press
the RETURN pushbutton on the current menu bar. The Mimic screen shows the internal
components of the UPS cabinet and a real-time graphical representation of the operating status
of the system.
Figure 33. MimicscreenandMainMenu.
6.4 Status Indicators
The four symbols on the left side of the control panel are status indicators. They are coloured
light emitting diode (LED) lamps, and they work in conjunction with the alarm horn to let you
know the operating status of the UPS.
Normal This green indicator is illuminated when the UPS is
operating in Normal mode. The Power Module is supplying
power to the critical load.
The indicator flashes when the system needs attention. The LCD
screen shows all active notices. Some notices may be accompanied
by an audible horn. To silence the horn, press any Control Panel
pushbutton once. The indicator may be flashing while other
indicators are illuminated. The indicator continues to flash until
acknowledged by pressing any Control Panel pushbutton once.
Battery This yellow indicator is illuminated when the UPS is operating
in Battery mode. Because Battery mode is a normal condition of
the UPS, the Normal indicator also remains illuminated.
Bypass This yellow indicator is illuminated when the UPS is operating
in Bypass mode. The critical load is supported by the bypass
source. The Normal indicator is not illuminated when the system
is in Bypass mode.
Alarm This red indicator is illuminated when a situation requires
immediate attention. The LCD screen shows the highest priority
active alarms. All alarms are accompanied by an audible horn. To
silence the horn, press any Control Panel pushbutton once. The
Alarm indicator may be illuminated along with other indicators.
The indicator flashes until acknowledged by pressing any
Control Panel pushbutton once.