Installation guide

UPS 40 – 160 kVA, 400V 50/60 Hz output
Users and Installation Guide
1023294
Revision C
55
UPS module Cable A Cable C Fuse 1
40 kVA 35 mm² 16 mm² 80 A
60 kVA 50 mm² 25 mm² 100 A
80 kVA 70 mm² 35 mm² 125 A
100 kVA 95 mm² 50 mm² 160 A
120 kVA 120 mm² 70 mm² 200 A
160 kVA 185 mm² 95 mm² 250 A
SPM Cable B Cable D Fuse 2
40 kVA 16 mm² 16 mm² 63 A
50 kVA 25 mm² 16 mm² 80 A
60 kVA 35 mm² 16 mm² 100 A
80 kVA 50 mm² 25 mm² 125 A
90 kVA 70 mm² 35 mm² 160 A
100 kVA 95 mm² 50 mm² 200 A
120 kVA 95 mm² 50 mm² 200 A
150 kVA 120 mm² 70 mm² 250 A
160 kVA 150 mm² 95 mm² 250 A
180 kVA 185 mm² 95 mm² 315 A
200 kVA 185 mm² 95 mm² 315 A
240 kVA 240 mm² 150 mm² 400 A
320 kVA 2 x 150 mm² 150 mm² 2 x 250 A or 500 A
400 kVA 2 x 185 mm² 185 mm² 630 A
480 kVA 2 x 300 mm² 300 mm² 800 A
640 kVA Busbar System 1000 A
Table 7. Recommendedcablesandfusesforthe(4)UPSwithSPMwiringdiagrams.
Required parallel system wiring length should be in accordance with the following rule, as
referenced to the diagram below, to ensure approximately equal current sharing, when in static
bypass mode:
Total length of 1A + 1B = Total length of 2A + 2B
= Total length of 3A + 3B
= Total length of 4A + 4B
This rule has a tolerance of approximately +/- 10% for the combined input and output wire
lengths. If installing only two UPS modules, this requirement is no longer required, as each
UPS is capable of supporting the full bypass requirement. However, this would preclude future
expansion.