12 Technical data
12.1 Standards
UPS 40 kVA 60,80 kVA 100, 120 kVA 160 kVA
Safety IEC/EN 62040-1-1, EN 60950
EMC IEC/EN 62040-2, UPS for restricted sales distribution
Product IEC/EN 62040-3
12.2 Environmental specification
UPS 40 kVA 60,80 kVA 100, 120 kVA 160 kVA
Amb. Temperature IEC/EN 62040-1-1, EN 60950
Relative humidity 0 to 95%, no condensation allowed
Storage –25°C to +60°C, excluding batteriesIEC/EN 62040-3
Altitude 1500 m above sea level
Vibration max 0.3 mm (2 to 9 Hz), max 1 m/s2 (9 to 200 Hz) sinusoidal
Noise (ISO7999) 65 dB(A) 70 dB(A)
Cooling air flow 588 liters/sec 1076 liters/sec
12.3 Mechanical configuration
UPS 40 kVA 60,80 kVA 100, 120 kVA 160 kVA
Dimensions
- Width
- Depth
- Height
519 mm
808 mm
1879 mm
944 mm
808 mm
1879 mm
Weight
- UPS
- Small BAT 38 Ah
- Small BAT 200WPC
- Large BAT 250WPC
- Large BAT 305WPC
- Large BAT 500WPC
313 kg
700 kg
1176 kg
1270 kg
1430 kg
2188 kg
313 kg
700 kg
1176 kg
1270 kg
1430 kg
2188 kg
480 kg
700 kg
1176 kg
1270 kg
1430 kg
2188 kg
530 kg
700 kg
1176 kg
1270 kg
1430 kg
2188 kg
Min. clearance
- Top
- Front
- Back, both side
460 mm (ventilation requirement)
915 mm (service requirement)
Colour RAL 9005 black
12.4 System input
UPS 40 kVA 60,80 kVA 100, 120 kVA 160 kVA
Rectifier input 3-phase + PE; Nominal Voltage 400 V 50/60 Hz;
Voltage tolerance -15% – +10% (max -30% – +20%); 45 – 65 Hz
Bypass input 3-phase + N + PE; Nominal Voltage 400 V 50/60 Hz; Voltage tolerance ±10%; ±3 Hz
Frequency 45 to 65 Hz
Input distortion ITHD 3% – 5% (1% VTHD mains input)
Power factor 0.99