Operating instructions
Table Of Contents

3-20
3-4 Technical Specification
Capacity 80kVA/64KW 120kVA/96KW
Rating Voltage V
220/380, 230/400, 240/415
(3Φ 4W+Earth)
Voltage Regulation % -25 ~ +20
Input Current Harmonic Distortion
(Full Load)
% < 5
PFC (Full Load) > 0.99
Frequency Hz 50 / 60
Input
Frequency Tolerance Hz 45 ~ 65
Output Voltage V 220/380, 230/400, 240/415 (3Φ 4W+Earth)
Output Frequency Hz 50 / 60
Total Harmonic (Linear Load) % ≦3
Voltage
Regulation
Static % ±1
Dynamic % ±7 (10% ~ 90% Linear Load)
Frequency
Regulation
Interior Oscillator Hz ±0.05
Synchronized % ±5
Output
Overload ≦125%: 10minutes ; ≦150%: 1minute
Battery Backup Intermittent Audible
Warning
UPS Abnormal Continuous
LED UPS status: Normal, Bypass, Backup and Fault
Display
LCD
Input/Output, Bypass, Inverter, Frequency, Loading and Battery voltage, current,
UPS abnormal message and intelligent self diagnosis
6 Integrated Dry-contacts
Remote
2 integrated Opto inputs
Standard RS232, Dry Contact Output
Interface
Optional SNMP card, Modbus card, Relay I/O control card, Environmental sensor
Parallel Operation Yes (up to 4 UPS of the same type (80/120kVA)
EPO Standard (Local and Remote)
SRAM Event Log Yes (500 records)
Parameter Configuration Yes
N+1 Module redundacy Feasible
Battery Temperature Compensation Optional
Others
Battery Start (Black Strat”) Yes
Normal % 94,5
Efficiency
ECO % 97
Transfer Time ms 0 ms
Temperature °C 0~40
Humidity (Non Condensed) % 90
Noise (One Meter) dBA 62-69
Dimension Width mm 520 520
Depth mm 910 975
Height mm 1165 1695
Overall
Weight Kg 259 384