Operating instructions

53
EN
Description
Adjustable parameters
Presetting
Ambient
temperature
high alarm
[enabled], [disabled]
If enabled, UPS alarm when ambient
temperature >40°C
enabled
EPO
operation
[normally open], [normally closed]
Normally open means UPS makes a
shutdown by a closing input state.
Normally closed means UPS makes a
shutdown by an opening input state.
Setting only available in UPS stand-by
mode.
normally
closed
Reset
Cumulative
Consumption
kWh
[no], [yes]
If “no”, no action.
If “yes”, the Cumulative Consumption
kWh value is cleared and the date and
time stamp for this statistic is set to the
current date and time.
no
Battery limit
time
5h, 6h, ...14h, 15h, 16h, …999h, disabled
Default “14h” means when work on
battery mode for more than 14 hours,
UPS will make bat low alarm and then
shutdown itself 30 minutes later even
battery voltage still above the
shutdown value.
Disabled means “No time limitation”
for battery mode
14h
Auto reboot
[enabled], [disabled]
Enabled means UPS will auto restart
to normal mode while utility recover
after the UPS has been shutdown for
battery low.
enabled
The UPS automatically restarts if utility returns after the output was shut
off due to exhausted batteries, a shutdown input signal, or automatic
shutdown command.
You can set the load segment for the amount of time to delay the restart
once utility returns, using the “Automatic Start Delay” setting. You can
also configure UPS restart to depend on the battery charge level, using
the “Battery Charge Capabilitiy % to Restart” setting.