Operating instructions

"UniVert 2" inverter
Page 35 of 42 8000012364 BAL, en
Protection class .............................IP 20
Cooling ..........................................Forced air cooling
Intake air temperature ...................At rated current 0°C to 45°C,
measured below the SBS
Storage temperature......................-20°C to +70°C
Ambient conditions ........................IEC 721 Part 3-3 Class 3K3 / 3Z1 /
3B1 / 3C2 / 3S2 / 3M3
Site altitude....................................Up to 2000 m above sea level
Mechanical stability
and vibration resistance.................In acc. with VDE 0160
Version 5.88 Item 7.2.2
Surface painted with ......................RAL 7032 (front panel)
Dimensions (W x H x D) ................483 x 174 x 400 mm
(19" x 4 height modules)
Weight ...........................................Approx. 13.5 kg
Noise generation ...........................< 50 dB(A)
Connection system
X1 AC mains input:........................Screw terminal 10 ... 25 mm
2
X2 AC output: ................................Screw terminal 10 ... 25 mm
2
X4 remote signals:.........................Screw terminal 0.2 ... 2.5 mm
2
PE conductor:................................M4 thread
X6 CAN bus interface ....................10-pin socket connector with
insulation displacement
connection system
in acc. with DIN 41651
X7 CAN bus interface ....................16-pin socket connector with
insulation displacement
connection system
in acc. with DIN 41651