Operating instructions

13
Battery type
sealed maintenance free (VRLA)
Protect C.1000
12 V 7 Ah x 3
Protect C.2000
12 V 7 Ah x 8
Protect C.3000
12 V 7 Ah x 8
Protect C.1000 BP 12 V 7 Ah x 3 x 2
Protect C.2030 BP 12 V 7 Ah x 8 x 2
Recharge time (to 90 %
of rated capacity)
~ 8 h (UPS with internal battery)
~ 24 h (with 1 additional battery)
~ 40 h (with 2 additional batteries)
Communication
Interfaces RS232 SUB-D (9-pin), USB
A
dditional: communication slot for
Extensions (eg, relay card, SNMP (Pro), ...)
Remote shutdown contact Potential-free (optionally programmable as
opener or closer)
Shutdown Software
on CD
“CompuWatch” for all popular operating
systems like:. Windows, Linux,
Mac, Unix, Novell, Sun
General data
Classification VFI SS 111 acc. to. IEC 62040–3
double conversion technology (INV / BATT)
VFI SS 311 acc. to IEC 62040–3
ECO mode
Full load efficiency
(AC-AC / DC-AC)
Protect C.1000 87 % / 85 %
Protect C.2000 88 % / 85 %
Protect C.3000 88 % / 85 %
Full load efficiency
(ECO / Transfer time
<10 ms) (economical
mode)
Protect C.1000 93 %
Protect C.2000 94 %
Protect C.3000 94 %
Inherent noise
(1 m distance)
Protect C.1000 44 dB (A)
Protect C.2000 49 dB (A)
Protect C.3000 49 dB (A)
Type of cooling
Forced cooling by variable speed fans
Operating temperature 0 °C to 45 °C Recommendation +15 °C
to +25 °C (due to battery system)
Storage temperature -15 °C to +60 °C (UPS)
0 °C to +35 °C (Battery)