Operating instructions
40
”Control” / Command Beschreibung
Go to Bypass / Normal Possibility to change
operation mode.
If the UPS is not in Normal Mode or
Bypass Mode this option is not used
and should not be displayed as a
control option.
Battery Test Schedule Battery Test:
yes | Cancel Battery test: no
Starts a manual battery test.
Reset Error State Reset Alarms: yes | no
Manually clears any latched alarms,
such as bad battery detected or DC
Bus over voltage/ under voltage.
With an active battery fault alarm,
the battery test status will also
simultaneously reset to “Not
Tested”.
7.3.5 IDENTIFICATION
Activate this menu item to view the following sub-menu items: “Type /
Model”, “Part number”, “Serial number” and finally the current “UPS
firmware” version one after the other.