Operating instructions

44
Description Adjustable parameters Presetting
A
mbient
temperature
warning
[enabled], [disabled]
If enabled, UPS alarm when ambient
temperature >40 °C
enabled
REPO
operation
[normally open], [normally closed]
Normally open means UPS makes a
shutdown by a closing input state.
Normally closed means UPS makes a
shutdown by an opening input state.
Setting only available in UPS stand-
by mode.
normally closed
Reset
Cumulative
Consumption
kWh
[no], [yes]
If “no”, no action.
If “yes”, the Cumulative Consumption
kWh value is cleared and the date
and time stamp for this statistic is set
to the current date and time.
no
Battery
limit time
5h, 6h, ...14h, 15h, 16h, …999h,
disabled
Default “14h” means when work on
battery mode for more than 14 hours,
UPS will make bat low alarm and then
shutdown itself 30 minutes later even
battery voltage still above the
shutdown value.
Disabled means “No time limitation”
for battery mode.
14h
A
uto reboot [enabled], [disabled]
Enabled means UPS will auto restart
to normal mode while utility recover
after the UPS has been shutdown for
battery low.
enabled