10.3 Maintenance Intervals
T
he maintenance schedule does not release the owner from
his/her obligation to create his/her own maintenance and operating
instructions for the location and to document them fully as quickly
as possible.
i
For recurrent measurements and measurements after repair
work as per BGV A3, compliance with the DIN VDE 0105-100
inspection intervals is mandatory.
Ongoing
Check the measured results of the equipment for plausibility.
Replace defective measuring instrumentation at the end of production.
Data bus:
Ongoing functional testing in operation.
Monthly
Test lamps and replace diodes if required.
Check the function of the system's internal measuring instrumentation
by comparing the values during operation with the values displayed.
Check the function of the measuring instruments and accessory
systems required for operation and maintenance.
Clean the outside of the ventilation grilles.
Every 6 months
Check the fastenings and function of the electrical connections in the
equipment.
Check the function of the fault current, differential current and fault
voltage protective circuits.
Carry out recurrent measurements in accordance with DIN VDE 0105.
Check the interior for damp and, if necessary, determine and rectify the
causes. Dry the equipment.
Clean the interior of the outdoor equipment.
Check door seals for dirt and damage and service or replace if
necessary.
Check the radial ventilators/fans in the cabinet ventilation system for
dirt and whether they are working correctly, and clean if necessary.
Replace defective ventilators/fans with original parts.
Cabinet ventilation:
Depending on the pollution degree, clean or replace air inlet filter mats.
Check the function of the heating units in the DC/AC and INV control
cabinet, especially before cold spells. No condensation may be present
in the equipment during operation.
Check the function of the overtemperature warning system by opening
the sensor path.