Page 94 of 100 8000041160 BAL
10.4 Repairs and Improvement
i
AEG PS will rescind all obligations such as warranty agree-
ments, service contracts, etc. entered into by AEG PS or its
representatives without prior notice, in the event of anything
other than original AEG PS spare parts being used.
Modifications to the Protect PV.6x0/8x0 may only be carried out by
AEG PS skilled personnel.
If you want other personnel to carry out this work, this will need to
be authorised by means of written approval from AEG PS.
Only original AEG PS spare parts (or spare parts purchased from
AEG PS) may be used.
10.4.1 Storing Spare Parts
i
When ordering spare parts, you must provide the component
designation, installation location and component number as
well as the unit number of the Protect PV.6x0/8x0.
AEG PS recommends that you have the following spare parts
available:
Item Component
F41.x DC input fuses,
l.v. h.b.c. fuse L2-2 1200 V
A12, A13 (optional) Remote signalling P8 - CCC
A91.1 Fan monitoring
M1 to M5 Radial fan (top of cabinet)
K7 AC output contactor
Table 28 - Spare parts
The AEG PS customer service department will be happy to send
you a complete spare parts list on request.
10.4.2 Testing After Repairs
Each time the equipment is repaired or modified, all recurrent
tests/measurements are to be carried out and documented in ac-
cordance with DIN VDE 0105 once the work is complete.