11 Decommissioning and Dismantling
The Protect PV-xxx-MH can be decommissioned or dismantled for
the purposes of changing its location or disposal.
Before beginning any work on the equipment, it must be de-
energised. For this purpose, the five safety rules of electrical
engineering in accordance with DIN VDE 0105 (EN 50110) must
be observed:
5 safety rules
1. Disconnect safely.
2. Secure the equipment against being switched back on.
3. Verify that all poles are de-energised.
4. Earth the equipment, close the earthing switch and short-
circuit the equipment.
5. Provide protection in the form of covers or barriers
for any neighbouring live parts.
i
The owner must draw up a safe disconnection procedure and
brief personnel on this.
11.1 Removing Connection Cables
Disconnect power connections on the DC and AC sides.
Disconnect the power supply and auxiliary power supply.
Disconnect all external control cables.
Disconnect the earthing line clips from the base structure and
in the low-voltage main distributor.
11.2 Dismantling
DANGER
Suspended loads during transport
Possibility of death or crushing.
Select lifting gear according to the total weight to be
transported.
Do not step under suspended loads.
Secure the danger zone.
Wear personal protective equipment.