Specifications
100
Error Messages Section 11-6
Byte address MB Description
Byte address +0 MB21 Write Coordination Byte
Byte address +1 MB22 Message Channel Low-byte
Byte address +2 MB23 Message Channel High-byte
Byte address +3 MB24 Function Key LED 1 to 4
Byte address +4 MB25 Function Key LED 5 to 8
Byte address +5 MB26 Function Key LED 9 to 12
Byte address +6 MB27 Function Key LED 13 to 16
Byte address +7 MB28 Function Key LED 17 to 20
Byte address +8 MB29 Function Key LED 21 to 24
Byte address +9 MB30 Function Key LED 25 to 28
Byte address +10 MB31 Function Key LED 29 to 32
Word-structured Memory Mapping
The data area comprises a maximum of 12 bytes (6 words).
Example: The cyclic data area is set to MW10 in the programming system.
Word address MW High-byte Low-byte
Word address +0 MW10 Write coordination byte Reserved
Word address +1 MW11 Message channel high-byte Message channel
low-byte
Word address +2 MW12 Function key LED 1 to 4 LED 5 to 8
Word address +3 MW13 Function key LED 9 to 12 LED 13 to 16
Word address +4 MW14 Function key LED 17 to 20 LED 21 to 24
Word address +5 MW15 Function key LED 25 to 28 LED 29 to 32
11.6 Error Messages
Code 1 Error from the data transmission-layer
Subcode
1E
SLAVE NOT READY ..........Slave not ready
2E
PROTOKOL ....................Sequence of the packets
3E
FRAME .........................Character frame error
4E
TIMEOUT.......................Timeout error
5E
CRC BCC......................CRC error
6E
PARITY.........................Parity error
7E
SEND ABORT .................Abort send process
8E
REC ABORT ...................Abort receive process
9E
BUF SIZE......................Insufficient cyclic buffer
10 E
NO DEFINE....................No cyclic data defined
12 E
DEFINE ........................Cyclic data already defined
15 E
NO PROTOCOL ...............Selected protocol is not sup-
ported
16 E
OVERRUN......................Receive buffer overrun
40 E
SYS ADDRESS ................Undefined system variable